Specific power consumption of HVAC system

Specific Power Consumption

Specific power consumption is the ratio of the power consumed by an engine to a certain force such as the amount of output the engine (equipment) produces. It allows engines (equipments) of all different sizes to be compared to see which is the most power efficient. It allows manufacturers to see which engine (equipment) will use the least power while still producing a high amount of output.

Specific power consumption of HVAC system
The ratio of power consumption (in KW) to the Tons of refrigeration effect produced.

Specific power consumption
= KW/TR rating

= Actual power consumed by the HVAC (KW input)/Tons refrigeration effect

=Compressor power, KW/ Net refrigeration capacity (TR)

If the compressor power is 120KW and net refrigeration capacity is 130 TR.

Then Specific power consumption = 120 KW/130 TR
                                                        = 0.92 KW/TR
                                                          

For find out HVAC Specific power consumption following procedure is carried out:

1)      Find out actual power consumed with the help of electric power analyzer
2)       Find out TR by


Net refrigeration capacity (TR) = M x Cp x Delta T/3024

For more click on below link....


Performance Assessment of Refrigeration Plants (TR)